GENERAL DATA
Dimension / b | 511 mm |
|---|---|
Dimension / h | 724 mm |
| Weight | 43,4 kg |
| Installation | Indoor and outdoor installation, tilt from 0-90 degrees (Fronius Shade Cover required for installation angles less than 15 degrees) |
Permitted humidity 2) | 0-100 % (non-condensing) |
| Dimension (width) | 511 mm |
| Dimension (height) | 724 mm |
| Dimension (depth) | 228 mm |
| Weight | 43,4 kg |
| Protection class | NEMA 4X |
| Night time consumption | <1 W |
| Inverter topology | Transformerless |
| Cooling | Variable speed fan |
| Elevation | 2000 m (6562 ft) with a max. input voltage of 1000 V / 3400 m (11155 ft) with a max. input voltage of 850 V |
| Certificates and compliance with standards | UL 1741-2010 Second Edition (incl. UL1741 Supplement SA 2016-09 for California Rule 21 and Hawaiian Electric Code Rule 14H), UL1998 (for functions: AFCI, RCMU and isolation monitoring), IEEE 1547-2003, IEEE 1547a-2014, IEEE 1547.1-2003, ANSI/IEEE C62.41, FCC Part 15 A & B, NEC 2017 Article 690, C22. 2 No. 107.1-16, UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013 |
| DC connection terminals | 6x DC+ and 6x DC- screw terminals for copper (solid / stranded / fine stranded) or aluminum (solid / stranded) |
| AC connection terminals | Screw terminals 14-6 AWG |
INPUT DATA
| Number of MPPT | 2 |
|---|---|
| Max. usable input current | 41,5 A |
Max. array short circuit current (1.5 * Imax) | 62,2 A |
Nominal input voltage | 350 V |
| Operating voltage range | 200-600 V |
MPP Voltage Range | 300-500 V |
Max. input voltage (Udc max) | 600 V |
OUTPUT DATA
| Max. output power 480 V | NA |
|---|---|
| Max. output power 277 V | NA |
| Max. output power 240 V | 11995 W |
| Max. output power 208 V | 11995 W |
Output configuration | 3~ NPE 208-240 V |
| Frequency range | 50-66 Hz |
| Nominal operating frequency | 60 Hz |
Power factor range | 0-1 ind,/cap, |
| Max continuous output current 480 V | NA |
| Max. continuous output current 277 V | NA |
| Max. continuous output current 240 V | 28,9 A |
| Max. continuous output current 208 V | 33,3 A |
PROTECTION DEVICES
| DC reverse polarity protection | Yes |
|---|---|
| Anti islanding | Internal; in accordance with UL 1741-2010, IEEE 1547-2003 and NEC |
| Over temperature protection | Output power derating /Active cooling |
| AFCI | Yes |
| Rapid shutdown compliant | Yes |
| Ground fault protection with isolation monitor interrupter | Yes |
| DC disconnect | Yes |
INTERFACES
| USB (A socket) | Datalogging and inverter update possible via USB |
|---|---|
| 2x RS422 (RJ45 socket) | Fronius Solar Net, interface protocol |
| Wi-Fi / Ethernet / Serial / Datalogger and webserver | Wireless standard 802.11 b/g/n / Fronius Solar.web, SunSpec Modbus TCP, JSON / SunSpec Modbus RTU |
| 6 inputs and 4 digital I/Os | Load management; signaling, multipurpose I/O |
Power Line Communication (PLC) | Yes – SunSpec Rapid Shutdown communication standard |