Cart0items

Description

Series4000Warranty3 Years
Volts12BCI921
Cells6Plates/Cell11
Terminal TypeDT
Included HardwareStainless Steel K-Lock Nut
Size & Thread5/16″-18
CablesOptional: 19″ 4/0 interconnect cable
Charge
Charge Voltage Range2.45-2.5 V/cell @ 25°C (77°F)
Float Voltage Range2.25 V/cell @ 25°C (77°F)
Recommended Charge Current25 A
Maximum Charge Current40 A
Self-Discharge Rate5%-10% per month at 25°C (77°F)
Capacity
Cold Crank Amps (CCA) 0°F / -18°C810
Marine Crank Amps (MCA) 32°F / 0°C1013
Reserve Capacity (RC @ 25A)406 Minutes
Reserve Capacity (RC @ 75A)107 Minutes
Capacity Affect by Temperature40°C
(104°F)
25°C
(77°F)
0°C
(32°F)
-15°C
(5°F)
105%100%75%50%
Hour RateCapacity / AMP HourCurrent / AMPs
@ 100 Hour Rate279 AH2.79 A
@ 72 Hour Rate265 AH3.68 A
@ 50 Hour Rate250 AH5 A
@ 20 Hour Rate210 AH10.5 A
@ 15 Hour Rate200 AH13.3 A
@ 10 Hour Rate185 AH18.48 A
@ 8 Hour Rate181 AH22.58 A
@ 5 Hour Rate166 AH33.18 A
@ 1 Hour Rate84 AH84 A
Ampere hour capacity ratings based on specific gravity of 1.280 at 27°C (80°F).
Reduce capacities 5% for specific gravity of 1.265 and 10% for 1.250.
Specifications
iso 9001Weight52 kg114.5 lbs
Length39.1 cm15.38“
Width17.8 cm7“
Height Inc. Term.36.5 cm14.38“
Product measurements & weights are calculated based on sample data. Individual specifications are subject to vary due to the manufacturing process & battery components.
Electrolyte Reserve51 mm2“
ContainerPolypropylene
CoverPolypropylene
HandlesRope / Plastic Handle

Voltage vs. Depth of Discharge

voltage vs depth of discharge 4000

Detailed Illustration

12 FS 185 HC

WAREHOUSE PICKUP

BRITISH COLUMBIA

PROVINCECITYPICKUP TIMEAVAILABILITY
BCDelta WarehouseMonday to Friday, 9:00 AM – 4:30 PMConfirm Availability
BCVictoria WarehouseMonday to Friday, 9:00 AM – 4:30 PMConfirm Availability

ALBERTA

PROVINCECITYPICKUP TIMEAVAILABILITY
ABCalgary WarehouseMonday to Friday, 9:00 AM – 4:30 PMConfirm Availability
ABEdmonton NW WarehouseMonday to Friday, 9:00 AM – 4:30 PMConfirm Availability

ONTARIO

PROVINCECITYPICKUP TIMEAVAILABILITY
ONBarrieMonday to Friday, 9:00 AM – 4:30 PMConfirm Availability

NOVA SCOTIA

PROVINCECITYPICKUP TIMEAVAILABILITY
NSHalifax WarehouseMonday to Friday, 9:00 AM – 4:30 PMConfirm Availability

DOWNLOADS

S12 185 Data Sheet                                         

Reviews

There are no reviews yet.

Be the first to review “Rolls S12 185 12V 210Ah Flooded Deep Cycle Battery – Group 921”

Your email address will not be published. Required fields are marked *