Series | FS | Warranty | 1 Year |
---|---|---|---|
Volts | 6 | BCI | GC2 |
Cells | 3 | Plates/Cell | 17 |
Terminal Type | DT | ||
Included Hardware | Stainless Steel K-Lock Nut | ||
Size & Thread | 5/16″-18 |
Charge | |
---|---|
Charge Voltage Range | 2.45-2.5 V/cell @ 25°C (77°F) |
Float Voltage Range | 2.25 V/cell @ 25°C (77°F) |
Self-Discharge Rate | 5%-10% per month at 25°C (77°F) |
Capacity | |
---|---|
Cold Crank Amps (CCA) 0°F / -18°C | 625 |
Marine Crank Amps (MCA) 32°F / 0°C | 781 |
Reserve Capacity (RC @ 25A) | 455 Minutes |
Reserve Capacity (RC @ 75A) | 119 Minutes |
Capacity Affect by Temperature | 40°C (104°F) |
25°C (77°F) |
0°C (32°F) |
-15°C (5°F) |
---|---|---|---|---|
105% | 100% | 75% | 50% |
Hour Rate | Capacity / AMP Hour | Current / AMPs |
---|---|---|
@ 100 Hour Rate | 301 AH | 3.01 A |
@ 72 Hour Rate | 296 AH | 4.11 A |
@ 50 Hour Rate | 280 AH | 5.59 A |
@ 20 Hour Rate | 235 AH | 11.75 A |
@ 15 Hour Rate | 223 AH | 14.88 A |
@ 10 Hour Rate | 207 AH | 20.68 A |
@ 8 Hour Rate | 202 AH | 25.26 A |
@ 5 Hour Rate | 186 AH | 37.13 A |
@ 1 Hour Rate | 94 AH | 94 A |
Ampere hour capacity ratings based on specific gravity of 1.280 at 27°C (80°F). Reduce capacities 5% for specific gravity of 1.265 and 10% for 1.250. |
Specifications | |||
---|---|---|---|
Weight | 29 kg | 64 lbs | |
Length | 25.9 cm | 10.19“ | |
Width | 18.1 cm | 7.13“ | |
Height Inc. Term. | 27.9 cm | 11“ | |
Product measurements & weights are calculated based on sample data. Individual specifications are subject to vary due to the manufacturing process & battery components. |
Electrolyte Reserve | 57 mm | 2.25“ | |
---|---|---|---|
Container | Polypropylene | ||
Cover | Polypropylene | ||
Handles | Top Molded Strap Brackets |
There are no reviews yet.