GENERAL DATA
Dimension / b | 511 mm |
---|---|
Dimension / h | 724 mm |
Weight | 41,68 kg |
Installation | Indoor and outdoor installation, tilt form 0-90 degrees (Fronius Shade Cover required for installation angles less than 15 degrees) |
Permitted humidity 2) | 0-100% (non-condensing) |
Dimension (width) | 511 mm |
Dimension (height) | 724 mm |
Dimension (depth) | 226 mm |
Weight | 41,68 kg |
Protection class | NEMA 4X |
Night time consumption | <1 W |
Inverter topology | Transformerless |
Cooling | Variable speed fan |
Elevation | 2000 m (6562 ft) with a max. input voltage of 1000 V / 3400 m (11155 ft) with a max. input voltage of 850 V |
Certificates and compliance with standards | UL 1741-2010 Second Edition (incl. UL1741 Supplement SA 2016-09 for California Rule 21 and Hawaiian Electric Code Rule 14H), UL1998 (for functions: AFCI, RCMU and isolation monitoring), IEEE 1547-2003, IEEE 1547a-2014, IEEE 1547.1-2003, ANSI/IEEE C62.41, FCC Part 15 A & B, NEC 2017 Article 690, C22. 2 No. 107.1-16, UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013 |
DC connection terminals | 6x DC+ and 6x DC- screw terminals for copper (solid / stranded / fine stranded) or aluminum (solid / stranded) |
AC connection terminals | Screw terminals 14-6 AWG |
UL safety standards & network regulations | UL 1741-2010, UL 1998, UL 1699B Issue 2-2013 |
INPUT DATA
Number of MPPT | 2 |
---|---|
Recommended PV Power (kWp) | 8,0 – 13,0 kWp |
Max. usable input current | 41,5 A |
Max. usable input current total (MPPT1 + MPPT2) | 41,5 A |
Max. array short circuit current (1.5 * Imax) | 62,2 A |
Nominal input voltage | 350 V |
Operating voltage range | 200-600 V |
MPP Voltage Range | 300-500 V |
Max. input voltage (Udc max) | 600 V |
OUTPUT DATA
Max. output power 480 V | NA |
---|---|
Max. output power 277 V | NA |
Max. output power 240 V | 9995 W |
Max. output power 208 V | 9995 W |
Output configuration | 3~ NPE 208-240 V |
Frequency range | 45-66 Hz |
Nominal operating frequency | 60 Hz |
Total harmonic distortion | < 1,5 % |
Power factor range | 0-1 ind,/cap, |
Max continuous output current 480 V | NA |
Max. continuous output current 277 V | NA |
Max. continuous output current 240 V | 24,0 A |
Max. continuous output current 208 V | 27,7 A |
OCPD/AC breaker size 480 V | NA |
OCPD/AC breaker size 208 V | 35 A |
Max. efficiency | 97 % |
CEC efficiency 240 V | 96,5 % |
CEC efficiency 208 V | 96,5 % |
PROTECTION DEVICES
DC reverse polarity protection | Yes |
---|---|
Anti islanding | internal; in accordance with UL 1741-2010, IEEE 1547-2003 and NEC |
Over temperature protection | Ouput power derating/Active cooling |
AFCI | Yes |
Rapid shutdown compliant | Yes |
Ground fault protection with isolation monitor interrupter | Yes |
DC disconnect | Yes |
INTERFACES
USB (A socket) | Datalogging and inverter update possible via USB |
---|---|
2x RS422 (RJ45 socket) | Fronius Solar Net, interface protocol |
Wi-Fi / Ethernet / Serial / Datalogger and webserver | Wireless standard 802.11 b/g/n / Fronius Solar.web, SunSpec Modbus TCP, JSON / SunSpec Modbus RTU |
6 inputs and 4 digital I/Os | Load management; signaling, multipurpose I/O |
Power Line Communication (PLC) | Yes – SunSpec Rapid Shutdown communication standard |