Input Data
Number of MPP trackers | 2 |
---|---|
Recommended PV Power (kWp) | 10.0 – 15.0 kW |
Max. usable input current | 33,0 / 18,0 A |
Max. usable input current total (MPPT1 + MPPT2)
|
51 A |
Max. array short circuit current (1.5 * Imax) | 49,5 / 27 A |
Nominal input voltage (Udc,r) | 425 V |
DC input voltage range (Udc min – Udc max)
|
80 – 600 V |
MPP voltage range (Umpp min – Umpp max)
|
260 – 480 V |
Max. input voltage | 1000 V |
Integrated DC string fuse holders | 4- and 4+ for MPPT 1 / no fusing required on MPPT 2 |
Output Data
Max. output power 240 V | 12,5 kVA |
---|---|
Max. output power 208 V | 12,5 kVA |
Output configuration
|
1~ NPE 208 / 240 V |
Frequency range | 45 – 66 Hz |
Frequency | 60 Hz |
Total harmonic distortion | < 2,5 % |
Power factor range
|
0 – 1 ind./cap. |
Max. continuous output current 240 V | 52,1 A |
Max. continuous output current 208 V | 60,1 A |
OCPD/AC breaker size 208 V | 80 A |
Max. efficiency | 97,9 % |
CEC efficiency 240 V | 96,5 % |
General Data
UL safety standards & network regulations | UL 1741-2015, UL 1998, UL 1699B Issue 2-2013 |
---|---|
Dimension / width | 1,68 ft |
Dimension / height | 2,46 ft |
Dimension / depth | 8,96 in |
Weight incl. packaging | 99,21 lb |
Weight | 82,45 lb |
Degree of protection | NEMA 4X |
Night-time consumption | < 1 W |
Inverter design | Transformerless |
Cooling | Variable speed fan |
Max. altitude | 4000 m (13120 ft) with a max. input voltage of 1000 V |
Certificates and compliance with standards | UL 1741-2010 Second Edition (incl. UL1741 Supplement SA 2016-09 for California Rule 21), UL1998 (for functions: AFCI, RCMU and isolation monitoring), IEEE 1547-2003, IEEE 1547.1-2003, ANSI/IEEE C62.41, FCC Part 15 A & B, NEC 2017 Article 690, C22. 2 No. 107.1-16, UL1699B Issue 2 -2013, CSA TIL M-07 Issue 1 -2013 |
DC connection technology | 4x DC+1, 2x DC+2 and 6x DC- screw terminals for copper (solid / stranded / fine stranded) or aluminum (solid / stranded) |
AC connection technology | Screw terminals 12 – 6 AWG |
Revenue Grade Metering | Optional (ANSI C12.1 accuracy) |
Interference emission class | B |
Protection Devices
DC reverse polarity protection | Yes |
---|---|
Anti islanding | internal in accordance with UL 1741-2016-09, IEEE 1547-2003 and NEC 2017 |
Over temperature protection | Output power derating / Active cooling |
AFCI | Yes |
Rapid shutdown compliant | Yes (according to NEC 2014) |
Ground fault protection with isolation monitor interrupter | Yes |
DC disconnector | Yes |
Interfaces
Wi-Fi / Ethernet LAN | Wireless standard 802.1 1 b/g/n / Fronius Solar.web, SunSpec Modbus TCP, JSON 1) |
---|---|
USB (type A socket) | Datalogging and inverter update possible via USB |
2x RS422 (RJ45 socket) | Fronius Solar Net |
Datalogger and web server | Optional 1) |
RS485 | SunSpec Modbus RTU |
6 inputs and 4 digital I/Os | Load management signaling, multipurpose I/O 1) |