Fluke 1587 FC Offers
PI/DAR timed ratio tests (1587 FC only)
Live circuit detection prevents insulation test if voltage > 30 V is detected for added user protection
VFD low-pass filter for accurate motor drive measurements (1587 FC only)
Auto-discharge of capacitive voltage for added user protection
Insulation test (1587 FC: 0.01 MΩ to 2 GΩ) (1577: 0.1 MΩ to 600 MΩ)
Insulation test voltages (1587 FC: 50 V, 100 V, 250 V, 500 V, 1000 V),(1577: 500 V, 1000 V) for many applications
AC/DC voltage, DC millivolts, AC/DC milliamps, Resistance (Ω), Continuity
Capacitance, diode test, temperature, Min/Max, frequency (Hz)(1587 FC only)
Auto power off to save battery power
CAT III 1000 V, CAT IV 600 V measurement category
Rugged, utility hard case allows you to bring everything you need for the job
Large display with backlight
Specifications:
Voltage DC
Maximum Voltage: 1000V
Maximum Resolution: 0.001V
Accuracy: ±(0.09%+2)
Voltage AC
Maximum Voltage: 1000V
Maximum Resolution: 0.1 mV
Accuracy: ±(2%+3)
Current DC
Maximum Amps: 400mA
Maximum Resolution: 0.01 mA
Amps Accuracy: ±(0.2%+2)
Current AC
Maximum Amps: 400mA
Maximum Resolution: 0.01 mA
Amps Accuracy: ±(1.5%+2)*
Resistance
Maximum Resistance: 50 MΩ
Maximum Resolution: 0.1Ω
Accuracy: ±(0.9%+2)
Insulation Test
Minimum Test Current @ 1kΩ/V:1mA
Test Voltages: 1577:500, 1000V
Maximum Resistance per Test Voltage: 50V; 100V; 250V; 500V; 1000V: 600 MΩ
Maximum Resolution per Test Voltage: 50V: 0.01 MΩ; 100V: 0.01 MΩ; 250V: 0.1 MΩ; 500V: 0.1 MΩ; 1000V: 0.1 MΩ
Accuracy per Test Voltage: 50V: ±(3% + 5); 100V: ±(3% + 5); 250V: ±(1.5% + 5)
General Specifications
Dimensions: 203x100x50mm (with holster)
Weight: 624g
Battery Life: Meter use: 1000 hours; Insulation test use: Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off.
IP Rating: IP40Fluke 1587 FC Offers
PI/DAR timed ratio tests (1587 FC only)
Live circuit detection prevents insulation test if voltage > 30 V is detected for added user protection
VFD low-pass filter for accurate motor drive measurements (1587 FC only)
Auto-discharge of capacitive voltage for added user protection
Insulation test (1587 FC: 0.01 MΩ to 2 GΩ) (1577: 0.1 MΩ to 600 MΩ)
Insulation test voltages (1587 FC: 50 V, 100 V, 250 V, 500 V, 1000 V),(1577: 500 V, 1000 V) for many applications
AC/DC voltage, DC millivolts, AC/DC milliamps, Resistance (Ω), Continuity
Capacitance, diode test, temperature, Min/Max, frequency (Hz)(1587 FC only)
Auto power off to save battery power
CAT III 1000 V, CAT IV 600 V measurement category
Rugged, utility hard case allows you to bring everything you need for the job
Large display with backlight
Specifications:
Voltage DC
Maximum Voltage: 1000V
Maximum Resolution: 0.001V
Accuracy: ±(0.09%+2)
Voltage AC
Maximum Voltage: 1000V
Maximum Resolution: 0.1 mV
Accuracy: ±(2%+3)
Current DC
Maximum Amps: 400mA
Maximum Resolution: 0.01 mA
Amps Accuracy: ±(0.2%+2)
Current AC
Maximum Amps: 400mA
Maximum Resolution: 0.01 mA
Amps Accuracy: ±(1.5%+2)*
Resistance
Maximum Resistance: 50 MΩ
Maximum Resolution: 0.1Ω
Accuracy: ±(0.9%+2)
Insulation Test
Minimum Test Current @ 1kΩ/V:1mA
Test Voltages: 1577:500, 1000V
Maximum Resistance per Test Voltage: 50V; 100V; 250V; 500V; 1000V: 600 MΩ
Maximum Resolution per Test Voltage: 50V: 0.01 MΩ; 100V: 0.01 MΩ; 250V: 0.1 MΩ; 500V: 0.1 MΩ; 1000V: 0.1 MΩ
Accuracy per Test Voltage: 50V: ±(3% + 5); 100V: ±(3% + 5); 250V: ±(1.5% + 5)
General Specifications
Dimensions: 203x100x50mm (with holster)
Weight: 624g
Battery Life: Meter use: 1000 hours; Insulation test use: Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off.
IP Rating: IP40
Specifications
Voltage DC Maximum Voltage 1000 V Accuracy ±(0.2%+2) Maximum Resolution 0.001V Voltage AC Maximum Voltage 1000 V Accuracy ±(2%+3) Maximum Resolution 0.1 mV Current DC Maximum Amps 400mA Amps Accuracy ±(1.0%+2) Maximum Resolution 0.01 mA Current AC Maximum Amps 400mA Amps Accuracy ±(2.0%+2) 1kHz bandwidth Maximum Resolution 0.01 mA Resistance Maximum Resistance 50 MΩ Accuracy ±(1.2%+2) Maximum Resolution 0.1Ω Insulation Test Minimum Test Current @ 1kΩ/V 1mA Test Voltages 500, 1000 V Maximum Resistance per Test Voltage 100V: 600 MΩ Maximum Resolution per Test Voltage 50V: 0.01 MΩ
100V: 0.01 MΩ
250V: 0.1 MΩ
500V: 0.1 MΩ
100V: 0.1 MΩ Accuracy per Test Voltage 50V: ±(3 % + 5)
100V: ±(3 % + 5)
250V: ±(1.5 % + 5)
500V: ±(2.0 % + 5)
100V: ±(2.0 % + 5) Environmental Specifications Operating temperature –20 °C to +55 °C Storage temperature -40°C to +60°C Humidity (Without Condensation) 0% – 95% (10 °C – 30 °C)
0% – 75% (30 °C – 40 °C)
0% – 40% (40 °C – 55 °C) Operating Altitude 2000 m Safety Specifications Overvoltage category Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement CAT III 1000 V and CAT IV 600 V Agency Approvals 2000 m CAT III 1000 V, CAT IV 600 V; 3000 m CAT II 1000 V, CAT III 600 V Mechanical & General Specifications Size 203 x 100 x 50 mm (with holster) Weight 624 g Warranty 3 years Battery life Alkaline Meter use 1000 hours Insulation test use Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off. IP Rating IP40 Click here for complete specifications on the Fluke 1587 FC
What’s included with the Fluke 1587 FC
Insulation Multimeter
Remote Probe
Test Leads
Alligator Clips
K-Type Thermocouple
Carrying Case
User Documentation
Two in one tools
Stand-alone tools
Insulation test features
1587 FC
1577
1503
1507
1550C
1555
Test voltages
50 V, 100 V, 250 V, 500 V, 1000 V
500 V, 1000 V
500 V, 1000 V
50 V, 100 V, 250 V, 500 V, 1000 V
250 V to 5000 V
250 V to 10,000 V
Insulation resistance range
0.01 MΩ to 2 GΩ
0.01 MΩ to 600 GΩ
0.01 MΩ to 2000 GΩ
0.01 MΩ to 10 GΩ
250 kΩ to 1 TΩ
250 kΩ to 2 TΩ
PI/DAR
Auto discharge
Timed ramp test (Breakdown)
Pass/fail comparison
Est. # of IRT tests
1000
1000
2000
2000
Various
Various
Voltage > 30 V warning
Memory
With Fluke Connect App
Remote test probe
Lo ohms/earth-bond continuity
200 mA source (10 mΩ resolution)
200 mA source (10 mΩ resolution)
Display
Digital LCD
Digital LCD
Digital LCD
Digital LCD
Digital LCD/ analog display
Digital LCD/ analog display
Hold/lock
Multimeter features
AC/DC volts
Note: Not all product features and specifications are listed in this table. For more complete information, see individual product data sheets.
Footnotes:
1. Function useful for checking connections and motor windings. Also useful for users who are required to perform earth-bond continuity measurements during installation testing.
2. Filter for variable-speed motor drive measurements.
Current
Resistance
Continuity beeper
Temperature (contact)
Lo-pass filter2
Capacitance
Diode test
Frequency
MIN/MAX
Other features
Backlight
Software
Fluke Connect compatible
FlukeView® Forms Basic
Fluke View® Forms Basic
Battery
4 AA (NEDA 15A or IEC LR6)
4 AA (NEDA 15A or IEC LR6)
4 AA (NEDA 15A or IEC LR6)
4 AA (NEDA 15A or IEC LR6)
Rechargeable
Rechargeable
Find out more about insulation testing
See it. Save it. Share it. All the facts, right in the field.
Fluke engineers have delivered an innovative mobile platform and tool that helps solve everyday problems, allowing you to instantly document measurements, retrieve historical data, and share live measurements with your team. All handled by the Android™ or iOS smart phone you already carry.
Fluke Connect with ShareLive™ video call is the only wireless measurement system that lets you stay in contact with your entire team without leaving the field. The Fluke Connect mobile app is works with over 20 different Fluke products – the largest suite of connected test tools in the world.
Make the best decisions faster than ever before by viewing temperature, mechanical, electrical and vibration measurements for each equipment asset in one place. Get started saving time and increasing your productivity.
Fluke Connect Features:
TrendIt™ Graphs: Use graphing to show changes in measurements, allowing you to graph and show problems instantly.
EquipmentLog™ History: Access equipment history building a database of equipment health and baselines with cloud backup.
ShareLive™ Video Calls: Save, collaborate and share measurements instantly with your team anytime, from anywhere.
AutoRecord™ Measurements: Instantly save measurements to your phone with Cloud backup.
Fluke Cloud™ Storage: Securely access equipment records anywhere, anytime.
Fluke Connect Benefits:
Maximize uptime
Minimize maintenance costs
Better assessments with accurate records
Higher efficiency with less walking around; no notebook and excel needed
Share troubleshooting knowledge live
Create and share helpful content in the field
Access to Fluke digital product manuals means no need to carry manuals in the field
Keep organized manually entered measurements
Webinar: Facilities Maintenance with Fluke
Proactive maintenance and energy savings strategies are essential for cost savings in facilities.
We’ve teamed up with Fluke to provide you with a thorough discussion on proactive maintenance strategies – approaches, tools, and the proper “health” measurements on critical assets. As managing energy costs are also critical, we will also explore how implementing an onsite compressed air and gas leak detection program, facilities can save tens of thousands of dollars annually and production equipment downtime. The latest test equipment advances have made it possible for users to perform leak inspections with little to no training in a fraction of the time versus conventional tools.
During this short webinar on Facilities Maintenance, we covered:Monitoring critical assets with fewer resources Bridging the skills gapWhy are we replacing the same bearings and seals over and over?What are the best tools to use? How do we justify the cost of the tools and resources?How do we start a Proactive Maintenance program?
Why you need the Fluke 1587 FC Insulation Multimeter
Insulation multimeters are an integrated tool for maintaining and troubleshooting motor systems, electrical distribution, and production equipment. Carrying the Fluke 1587 FC will enable you to test insulation more often, making your maintenance tests more thorough and your troubleshooting more effective.
This multimeter combines a TRMS digital multimeter and a digital insulation tester in a single, compact unit. For this reason, it is capable of measuring a higher resistance than the average multimeter; allowing you to know when a cable is leaking under high voltage – see 0:25.
Its compatibility with Fluke Connect® makes it even more of an asset in your toolbox! Find out why at 0:58.
How To Take Insulation Resistance Measurements with the Fluke 1587FC
This video will teach the viewers how to take insulation resistance measurements with this insulation multimeter. It also shows the viewers where functions that relate to insulation resistance are on the device. Additionally, this test instrument is Fluke Connect compatible.
How To Test a Motor with the Fluke 1587 FC Insulation Meter
Use the Fluke Connect App to save the measurements taken for a later date. To test a motor, follow the simple step-by-step instructions provided in the video. You’ll complete a motor test in no time at all.
Fluke 1587 FC Tips and Tricks: Low-Pass Filter
Get step-by-step instructions on using a VFD drive and the 1587 FC. By connecting the unit to a smartphone or tablet via Bluetooth, you can see your measurements in current time.
There are no reviews yet.